| MODEL |
Galleon 1K(L)
|
Galleon 1.5K |
Galleon 2K(L)
|
Galleon 3K(L)
|
Galleon 6K(L) |
Galleon 10K(L) |
| Capacity |
1000 VA / 800 W |
1500 VA / 1200 W |
2000 VA / 1600 W |
3000 VA / 2400 W |
6000 VA / 4800 W |
10000 VA / 8000 W |
| INPUT |
| Voltage Range |
Low Line Transfer |
160 VAC / 140 VAC / 120 VAC / 110 VAC ¡Ó 5 % or
80 VAC / 70 VAC / 60 VAC / 50 VAC ¡Ó 5 %
(based on load percentage 100% - 80% / 80% - 70% / 70% - 60% / 60% -0) |
176 VAC @ 100% load
110 VAC @ 50% load |
| Low Line Comeback |
175 VAC ¡Ó 5 % or 85 VAC ¡Ó 5 % |
186 VAC @ 100% load
120 VAC @ 50% load |
| High Line Transfer |
300 VAC ¡Ó 5 % or 150 VAC ¡Ó 5 % |
300 VAC |
| High Line Comeback |
290 VAC ¡Ó 5 VAC or 143 VAC ¡Ó 3 VAC |
290 VAC |
| Frequency Range |
47.5 Hz ~ 52.5 Hz or 57 Hz ~ 63 Hz |
46 ~ 54 Hz @ 50 Hz/56 ~ 64 Hz @ 60 Hz |
| Phase |
Single phase with ground |
| Power Factor |
¡Ù 0.95 |
¡Ù 0.99 @ 100% load |
| OUTPUT |
| AC Voltage Regulation (Batt. Mode) |
¡Ó3% |
¡Ó 1% |
| Frequency Range (Synchronized Range) |
48 ~ 52 Hz or 57 ~ 63 Hz |
46 ~ 54 Hz @ 50 Hz/56 ~ 64 Hz @ 60 Hz |
| Frequency Range (Batt. Mode) |
50 Hz ¡Ó 0.25 Hz or 60 Hz ¡Ó 0.3 Hz |
50/60 Hz ¡Ó 0.1 Hz |
| Current Crest Ratio |
3 : 1 |
| Harmonic Distortion |
¡Ø 3 % THD (Linear Load)
¡Ø 6 % THD(Non-linear Load) |
¡Ø 4 % THD (Linear Load)
¡Ø 7 % THD (Linear Load) |
¡Ø 2 % THD (Linear Load)
¡Ø 6 % THD (Linear Load) |
| Transfer Time |
AC to DC |
Zero |
| Inverter to Bypass |
4 ms (Typical) |
Zero |
| Waveform (Batt. Mode) |
Pure Sine Wave |
| EFFICIENCY |
| To AC Mode |
~ 85 % |
~ 88 % |
90 % |
| To Battery Mode |
83 % |
88 % |
| BATTERY |
| Standard Model |
Battery Type |
12 V / 7 AH |
12 V / 9 AH |
12 V / 7 AH |
12 V / 9 AH |
12 V / 7 AH |
12 V/ 9 AH |
| Numbers |
3 |
3 |
6 |
6 |
20 |
20 |
| Typical Recharge Time |
4 hours recover to 90% capacity |
7 hours recover to 90% capacity |
8 hours recover to 90% capacity |
| Charging Current (max.) |
1.0 A |
1.0 A |
| Charging Voltage |
41.0 VDC ¡Ó 1% |
82.1 VDC ¡Ó 1% |
273.0 VDC |
| Long-run Model |
Battery Type |
Depending on the capacity of external batteries |
| Numbers |
| Charging Current (max.) |
8.0 A |
4.0 A |
| Charging Voltage |
41.0 VDC ¡Ó 1% |
82.1 VDC ¡Ó 1% |
273.0 VDC
|
| INDICATORS |
| LCD Panel |
UPS status, Load level, Battery level, Input/Output voltage, Discharge tiumer, and Fault conditions |
| LED Panel |
UPS status, Load level, Battery level, and Fault indicators |
| ALARM |
| Battery Mode |
Sounding every 4 seconds |
| Low Battery |
Sounding every second |
| Overload |
Sounding twice every second |
| Fault |
Continuously sounding |
| PHYSICAL |
| Dimension, D X W X H (mm) |
338.5 X 145 X 220 |
387 X 190 X 318 |
526 X 250 X 576.5 |
| Net Weight (kgs) |
14 |
7 |
14 |
29.5 |
16 |
29.5 |
16 |
90 |
35 |
93 |
38 |
| OPERATING ENVIRONMENT |
| Humidity |
20-90 % RH @ 0- 40¢XC (non-condensing) |
| Noise Level |
Less than 50dB @ 1 Meter |
Less than 55dB @ 1 Meter |
| MANAGEMENT |
| Smart RS-232/USB |
Supports Windows 98 SE/ME/NT 4.x/2000/2003/XP/Vista/2008 |
| Optional SNMP |
Power management from SNMP manager and web browser |