| MODEL |
Megatron 600 |
Megatron 1.2K |
Megatron 2.4K
|
| Capacity |
600 VA/ 360 W |
1200 VA/ 7200 W |
1200 VA/ 1440 W |
| INPUT |
| Voltage |
Nominal Voltage |
120 VAC or 220/230/240 VAC |
| Acceptable Voltage Range |
0-160 VAC / 0-300 VAC |
| Frequency Range |
60/50 Hz (auto sensing) |
| OUTPUT |
| AC Voltage Regulation (Batt. Mode) |
¡Ó10% |
| Frequency Range (Batt. Mode) |
60 Hz or 50 Hz ¡Ó1 Hz |
| Transfer Time |
10 ms typical |
| Waveform (Batt. Mode) |
Simulated Sine Wave |
| Peak Efficiency (AC Mode) |
> 95% @ Rated R load and battery full charged |
| BATTERY & CHARGER |
| Battery Voltage |
12 VDC |
12 VDC |
24 VDC |
| Floating Charge Voltage |
13.7 VDC ¡Ó0.2 VDC |
27.4 VDC ¡Ó0.4 VDC |
| Low Battery Alarm Voltage |
10.5 VDC ¡Ó0.4 VDC |
21.0 VDC ¡Ó0.8 VDC |
| Shutdown Voltage |
10.0 VDC ¡Ó0.4 VDC |
20.0 VDC ¡Ó0.8 VDC |
| Overcharge Protection |
15.0 VDC ¡Ó0.4 VDC |
30.0 VDC ¡Ó0.8 VDC |
| Maximum Charge Current |
10 A¡Ó 1 A, Optional for 20 A ¡Ó 1 A |
| PROTECTION |
| Full Protection |
Overload and short circuit protection |
| INDICATORS |
| Battery Mode |
Battery Mode (Yellow) LED lighting |
| Charging Mode |
Charge Mode (Green) LED flashing every 5 seconds |
| Battery Capacity |
4 Green LEDs indicating battery capacity. Charge Mode LED and 4 Battery Capacity LEDs are lighting when battery is fully charged |
| Over-charge |
Charge Mode LED and battery capacity LEDs flashing every 2 seconds |
| Overload |
Overload (Yellow) LED flashing every 2 seconds |
| Over-temperature |
Over Temp. (Red) LED flashing every 2 seconds |
| Fault |
All LEDs are flashing every 2 seconds |
| ALARM |
| Battery Mode |
Sounding every 10 seconds |
| Low Battery |
Sounding every 2 seconds |
| Overload |
Sounding every 0.5 second |
| Over Temperature |
Continuously sounding |
| Fault |
Continuously sounding |
| PHYSICAL |
| Dimension, D X W X H (mm) |
141.2 x 255 x 352 |
| OPERATING ENVIRONMENT |
| Humidity |
0 to 90% Relative Humidity(Non-condensing) |
| Operating Temperature |
0¢J to 40¢J |
| Storage Temperature |
-15¢J to 50¢J |