Frigate Dual 1KVA/2KVA/3KVA Online UPS
Frigate Dual 1KVA/2KVA/3KVA Online UPS

Frigate Dual series is specially designed to accept a broad range of worldwide utility no matter it’s in high-voltage or low-voltage environment. It automatically accepts two input ranges of 88 to 144 VAC and 176 to 288 VAC. The output is precisely regulated and sustained even though it’s fully loaded. An isolation transformer is used to galvanically isolate the output from AC input. The UPS will offer full isolation and complete common mode noise rejection from connected precious equipment.

Frigate Dual 1KVA/2KVA/3KVA Online UPS
Main Features
  • True double-conversion
  • Accepts dual-mains inputs for special power environment with high Voltage and Low Voltage
  • Complete galvanic isolation design offers full isolation and complete common mode noise rejection
  • Wide input voltage range (88-144VAC and 176-288VAC) at full load
  • Selectable output voltage at 110VAV or 220VAC
  • Input power factor correction 0.99
  • Output voltage regulation < ± 1%
  • RS-232 communication port or mini slot for USB / RS-232 / AS400 / SNMP communication
  • Smart battery charger design for optimized battery performance


ModelFrigate Dual 1K(L)Frigate Dual 2K(L)Frigate Dual 3K(L)
PHASESingle phase with ground
CAPACITY1000 VA / 800 W2000 VA / 1600 W3000 VA / 2400 W
INPUT
Voltage Range88-144 VAC and 176 - 288 VAC (Auto sensing)
Frequency Range45Hz ~ 55 Hz or 56Hz ~ 65 Hz
Power Factor≧ 0.99 @ Nominal Voltage (100% Load)
OUTPUT
Output Voltage110/115/120/127 VAC or 208/220/230/240 VAC
AC Voltage Regulation (Static)± 1%
Frequency Range (Synchronized Range)47 Hz ~ 53 Hz or 57 Hz ~ 63 Hz
Frequency Range (Batt. Mode)50 Hz ± 0.2 Hz or 60Hz ± 0.2 Hz
Current Crest Ratio3:1
Harmonic Distortion≦ 2 % THD (Linear Load) ; ≦ 6 % THD (Non-linear Load)
Transfer TimeAC Mode to Batt. ModeZero
AC Mode to Bypass4 ms (Typical)
Bypass to AC Mode4 ms (Typical)
Waveform (Batt. Mode)Pure Sinewave
EFFICIENCY(Peak)
AC Mode (@100% RCD load)76% (Typical); 78% (Peak)77% (Typical); 79% (Peak)78% (Typical); 80% (Peak)
Battery Mode(@100% RCD load)84% (Typical); 86% (Peak)86% (Typical); 88% (Peak)87% (Typical); 89% (Peak)
ECO Mode85%88%90%
BATTERY
Standard ModelBattery Type12V / 9Ah12V / 9Ah12V / 9Ah
Numbers246
Typical Recharge Time5 hours recover to 90% capacity
Charging Current (Max.)1.0 A
Charging Voltage27.4 VDC ± 1%54.8 VDC ±1%82.2 VDC ±1%
Long-run ModelBattery Type and NumbersDepending on applications
Charging Current (Max.)4A or 8A
Charging Voltage27.4 VDC ± 1%54.8 VDC ±1%82.2 VDC ±1%
INDICATORS
LCD DisplayUPS status, Load level, Battery level, Inpute/Output/battery info, Discharge timer, and Fault conditions
ALARM
Battery ModeSounding every 4 seconds
Low BatterySounding every second
OverloadSounding twice every second
FaultContinously sounding
PHYSICAL
Standard ModelDimension, DxWxH (mm)423 x 145 x 332426 x 190 x 448426 x 190 x 448
Net Weight (kgs)26.53456
Long-run ModelDimension, DxWxH (mm)423 x 145 x 332426 x 190 x 448426 x 190 x 448
Net Weight (kgs)21.52341
ENVIRONMENT
Operation Humidity20-95 % RH @ 0- 40°C (Non-condensing)
Noise LevelLess than 50dBA @ 1 Meter
MANAGEMENT
CommunicationRS232 Card / Optional USB Card, SNMP Card, or AS400 Card
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix, and MAC
Optional SNMPPower management from SNMP manager and web browser
* L means long-run model
Product specifications are subject to change without further notice
Download

Frigate Dual 1KVA/2KVA/3KVA - Brochure
Frigate Dual 1KVA/2KVA/3KVA - User's Manual